Energy-efficient
The use of high efficiency scroll compressor, high efficiency V/A finned heat exchanger, great design of liquid head and more reasonable internal layout, make the airflow field inside the air conditioning more uniform, refrigerant distribution more reasonable, thus greatly improving the heat transfer efficiency of the heat exchanger, so that the air conditioning unit to achieve high energy efficient effect.
Infrared humidifying
Adopt advanced infrared humidifying, it greatly reduct the dependency of humidifier on water quality,makes the temperature faster and more accurate
Multiply protection
Perfect self diagnostic and self alarm function, effectively prevent failure and seek problem faster, protects the units in all aspects and prolongs the service life of air conditioner
Convenient and durable
Unique modular design, compact structure, small size, stable and sturdy, easy to split, meet the delivery requirements under the limit conditions. Insulated cotton adopted, great insulation performance. universal accessories of single and double doors, greatly reduct the size of vulnerable accessory
Environmental refrigerant
Adapt to the international requirements of environmental refrigerant, using R410A environmental refrigerant
Convenient maintenance
The whole unit adopts complete front door, all parts of maintenance can be carried out in the front, saving the use of space.
Compressor and other parts can be welded to facilitate maintenance.
Product Name |
Part No. |
Part No. |
Room level air cooling precision air conditioner indoor unit |
DAR12-N3-123 |
Refrigerating capacity: 12.5kW.Air returning working condition: dry bulb temperature 24C, wet-bulb temperature 17°C; Air blowing rate:3000m h, air blowing excess pressure75Pa, Size: W6O0*D570*H2000mm, RS485 communication interface, to pair blowing, front air returning, Full load current 17.4, Electric heating capacity 4KW, humidification capacity:.3KGIH |
Room level air cooling precision air conditioner indoor unit |
DAR26-N4-123 |
Refrigerate Refrigerating capacty:.26.34kW.Air returning working condition. dry bulbtemperature24C,wet-bulb temperature 17'C;Air blowing rate.7500m3/h, EC draught fan, Electric heating capacity6KW, humidification capacity.4.5KGIH, Size: W923*D1010*H1980mm, RS485 communication interface, 7" colorful touchscreen, single vortex compressor, R410A(not filled), tuyere induced, top air blowing, front air returning, The height of floor should be higher than400mm at least, compatible up and blowpipes, liquid pipe q:15.88, air pipe o.:22.23, humidifier water supply pipe(19.05mm internal thread) G3/4, condensing drain pipe q19,voltage380V, maximum power of indoor unit 18.6KW, maximum power of outdoor unit 1.2KW |
Room level air cooling precision air conditioner indoor unit |
DAR31-N4-123 |
Refrigerating capacity: 31.2kW. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate: 9000m3/h, EC draught fan, Electric heating capacity 6KW, humidification capacity: 4.5KG/H, size: W 923* D1010* H1980mm, RS485 communication interface, 7'' colorful touch screen, single vortex compressor, R410A(not filled), tuyere included, top air blowing, front air returning, The height of floor should be higher than 400mm at least; pipes on left, liquid pipe φ: 15.88, air pipe φ:22.23, humidifier water supply pipe(19.05mm internal thread)G3/4‘', condensing drainpipeφ19(pagodajoint+hoseclamp),voltage380V, maximum power of indoor unit21.6KW, maximum power of outdoor unit 2.2KW |
Room level air cooling precision air conditioner indoor unit |
DAR35-N4-123 |
Refrigerating capacity: 35.06kW. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate: 10500m3/h, EC draught fan, Electric heating capacity 6KW, humidification capacity: 4.5KG/H, size: W 923* D1010* H1980mm, Rs485 communication interface, 7'' colorful touch screen, single vortex compressor, R410A(not filled), tuyere included, top air blowing, front air returning, The height of floor should be higher than 400mm at least; pipes on left, liquid pipe φ: 15.88, air pipe φ: 22.23, humidifier water supply pipe(19.05mm internal thread)G3/4‘', condensing drainpipeφ19(pagodajoint+hoseclamp),voltage380V, maximum power of indoor unit 22.7KW, maximum power of outdoor unit 2.2KW |
Room level air cooling precision air conditioner indoor unit |
DAR41-N4-123 |
Refrigerating capacity: 40.55kW. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate: 10500m3/h, EC draught fan, Electric heating capacity 6KW, humidification capacity: 4.5KG/H, size: W 923* D1010* H1980mm, RS485 communication interface, 7'' colorful touch screen, single vortex compressor, R410A(not filled), tuyere included, top air blowing, front air returning, The height of floor should be higher than 400mm at least; pipes on left, liquid pipe φ: 15.88, air pipe φ: 22.23, humidifier water supply pipe(19.05mm internal thread)G3/4‘', condensing drain pipeφ19(pagodajoint+hoseclamp),voltage380V, maximum power of indoor unit 22.7KW, maximum power of outdoor unit 2.2KW |
Room level air cooling precision air conditioner indoor unit |
DAR45-N4-123 |
Refrigerating capacity: 45.02kW. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate: 12000m3 /h, EC draught fan, Electric heating capacity 6KW, 4.5KG/H Infrared humidifier, size: W 92 3* D1010* H 1980mm, RS485 communication interface, air returning humiture 24℃, 50%RH, 7 '' colorful touch screen, single Danfoss vortex compressor, R410A(not filled), tuyere included, top air blowing, front air returning, The height of floor should be higher than 400mm at least; pipes on left, liquid pipe φ: 15.88, air pipe φ: 22.23, humidifier water supply pipe(19.05mm internal thread) G3/4‘', condensing drain pipe φ19(pagoda joint+hoseclamp), voltage 380V, maximum power of indoorunit24.9KW, maximum power of outdoor unit 2.5KW |
Room level air cooling precision air conditioner indoor unit |
DAR53-N4-123 |
Refrigerating capacity: 52.69k W. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate: 15000m3 /h, E C draught fan, Electric heating capacity 9KW, humidification capacity: 6.5KG/H, size: W1823* D1010* H1980mm, RS485 communication interface, 7 '' colorful touch screen, double Copeland vortex compressor, R410A(not filled), tuyere included, top air blowing, front air returning, The height of floor should be higher than 400mm at least; pipes on left, liquid pipe φ: 15.88, air pipe φ: 22.23, humidifier water supply pipe(19.05mm internal thread) G3/4‘', condensing drain pipe φ19(pagoda joint +hoseclamp), voltage 380V, maximum power of indoor unit 34.2KW, maximum power of outdoor unit 2*1.2KW |
Room level air cooling precision air conditioner indoor unit |
DAR62-N4-123 |
Refrigerating capacity: 62..4k W. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate: 18000m3 /h, E C draught fan, Electric heating capacity 9K W, 6 .5KG/H Infrared humidifier, size: W1823* D1010* H 1980mm, RS485 communication interface, air returning humiture 24℃, 50%RH, 7 ' ' colorful touch screen, double Danfoss vortex compressor, R410A(not filled), tuyere included, top air blowing, front air returning, The height of floor should be higher than 400mm at least; pipes on left, liquid pipe φ: 15.88, air pipe φ: 22.23, humidifier water supply pipe(19.05mm internal thread) G3/4‘', condensing drain pipe φ19(pagoda joint+hoseclamp), voltage 380V, maximum power of indoorunit40.1KW, maximum power of outdoor unit 2*2.2KW |
Room level air cooling precision air conditioner indoor unit |
DAR70-N4-123 |
Refrigerating capacity: 70.1k W. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate: 21000m3 / h, EC draught fan, Electric heating capacity 9KW, humidification capacity: 6.5KG/H, size: W1823* D1010* H 1980mm, RS485 communication interface, 7 ' ' colorful touch screen, double vortex compressor, R410A(not filled), tuyere included, top air blowing, front air returning, The height of floor should be higher than 400mm at least; pipes on left, liquid pipe φ: 15.88, air pipe φ: 22.23, humidifier water supply pipe(19.05mm internal thread)G3/4‘', condensing drainpipeφ19(pagodajoint+hoseclamp),voltage380V, maximum power of indoor unit 41.3KW, maximum power of outdoor unit 2*2.2KW |
Room level air cooling precision air conditioner indoor unit |
DAR80-N4-123 |
Refrigerating capacity: 80.22kW. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate: 23000m3 / h, EC draught fan, Electric heating capacity 9KW, humidification capacity: 6.5KG/H, size: W1823* D1010* H1980mm, RS485 communication interface, 7 ' 'colorful touch screen, double vortex compressor, R410A(not filled), tuyere included, to pair blowing, front air returning, The height of floor should be higher than 400mm at least; pipes on left, liquid pipe φ: 15.88, air pipe φ:22.23, humidifier water supply pipe(19.05mm internal thread)G3/4‘', condensing drainpipeφ19(pagodajoint+hoseclamp),voltage380V, maximum power of indoor unit 42.5KW, maximum power of outdoor unit 2*2.2KW |
Room level air cooling precision air conditioner indoor unit |
DAR90-N4-123 |
Refrigerating capacity: 90.03kW. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate:24000m3 / h, E C draught fan, Electric heating capacity 9K W, 6 .5KG/H Infrared humidifier, size: W1823* D1010* H 1980mm, RS485 communication interface, air returning humiture 24℃, 50%RH, 7 ' ' colorful touch screen, double Danfoss vortex compressor, R410A(not filled), tuyere included, top air blowing, front air returning, The height of floor should be higher than 400mm at least; pipes on left, liquid pipe φ: 15.88, air pipe φ: 22.23, humidifier water supply pipe(19.05mm internal thread) G3/4‘', condensing drain pipe φ19(pagoda joint+hoseclamp), voltage 380V, maximum power of indoorunit46.8KW, maximum power of outdoor unit2*2.5KW |
Room level air cooling precision air conditioner indoor unit |
DAR00-N4-123 |
Refrigerating capacity: 100.22k W. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate: 25600m3 / h, E C draught fan, Electric heating capacity 9K W, humidification capacity: 6.5KG/H, size: W1823* D1010* H 1980mm, RS485 communication interface, 7 ' ' colorful touch screen, double vortex compressor, R410A(not filled), tuyere included, to pair blowing, front air returning, The height of floor should be higher than 400mm at least; pipes on left, liquid pipe φ: 15.88, air pipe φ:22.23, humidifier water supply pipe(19.05mm internal thread) G3/4‘', condensing drain pipe φ19(pagoda joint+hoseclamp), voltage 380V, maximum power of indoor unit 51KW, maximum power of outdoor unit 2*2.5KW |
Room level air cooling precision air conditioner indoor unit |
DAR26-N5-123 |
Refrigerating capacity: 26.34kW. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate: 9000m3/h, EC draught fan, Electric heating capacity 6K W, humidification capacity: 6.5KG/H, size: W923* D1010* H 1980mm, RS485 communication interface, 7 ' ' colorful touch screen, single vortex compressor, R410A(not filled), tuyere not included, sinking air supply, top air returning, The height of floor should be higher than 400mm at least; pipes on left, liquid pipe φ: 15.88, air pipe φ:22.23, humidifier water supply pipe(19.05mm internal thread) G3/4‘', condensing drain pipe φ19(pagoda joint+hoseclamp), voltage 380V, maximum power of indoor unit 18.6KW, maximum power of outdoor unit 1.2KW |
Room level air cooling precision air conditioner indoor unit |
DAR31-N5-123 |
Refrigerating capacity: 31.2kW. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate: 9000m3/h, EC draught fan, Electric heating capacity 6K W, humidification capacity: 6.5KG/H, size: W923* D1010* H 1980mm, RS485 communication interface, 7 ' ' colorful touch screen, single vortex compressor, R410A(not filled), tuyere not included, sinking air supply, top air returning, The height of floor should be higher than 400mm at least; pipes on left, liquid pipe φ: 15.88, air pipe φ: 22.23, humidifier water supply pipe(19.05mm internal thread) G3/4‘', condensing drain pipe φ19(pagoda joint+hoseclamp), voltage 380V, maximum power of indoor unit 21.6KW, maximum power of outdoor unit 2.2KW |
Room level air cooling precision air conditioner indoor unit |
DAR35-N5-123 |
Refrigerating capacity: 35.06kW. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate: 10500m3 / h, E C draught fan, Electric heating capacity 6K W, humidification capacity: 6.5KG/H, size: W923* D1010* H1980mm, RS485 communication interface, 7 ' ' colorful touch screen, single vortex compressor, R410A(not filled), tuyere not included, sinking air supply, top air returning, The height of floor should be higher than 400mm at least; pipes on left, liquid pipe φ: 15.88, airpipe φ: 22.23, humidifier water supply pipe(19.05mm internal thread) G3/4‘', condensing drain pipe φ19(pagoda joint+hoseclamp), voltage 380V, maximum power of indoor unit 22.2KW, maximum power of outdoor unit 2.2KW |
Product Name |
Part No. |
Part No. |
Room level air cooling precision air conditioner indoor unit |
DAR41-N5-123 |
Refrigerating capacity: 40.55kW. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate: 11500m3 /h, E C draught fan, Electric heating capacity 6K W, humidification capacity: 4.5KG/H, size: W1823* D1010* H1980mm, RS485 communication interface, 7 ''colorful touch screen, single vortex compressor, R410A(not filled), tuyere not included, sinking air supply, top air returning, The height of floor should be higher than 400mm at least; pipes on left, liquid pipe φ: 15.88, air pipe φ: 22.23, humidifier water supply pipe(19.05mm internal thread) G3/4‘', condensing drain pipe φ19(pagoda joint+hoseclamp), voltage 380V, maximum power of indoor unit 22.7 KW, maximum power of outdoor unit 2.2KW |
Room level air cooling precision air conditioner indoor unit |
DAR45-N5-123 |
Refrigerating capacity: 45.02kW. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate: 12000m3 /h, E C draught fan, Electric heating capacity 6K W, 4.5KG/H Infrared humidifier, size: W923* D1010* H 1980mm, RS485 communication interface, air returning humiture 24℃, 50%RH, 7 ''colorful touch screen, single vortex compressor, R410A(not filled), tuyere not included, sinking air supply, top air returning, Theheightoffloorshouldbehigherthan400mmatleast;pipes on left,liquidpipeφ:15.88,airpipeφ: 22.23, humidifier water supply pipe(19.05mm internal thread) G3/4‘', condensing drain pipeφ19(pagoda joint+hoseclamp), voltage 380V, maximum power of indoorunit24.9 KW, maximum power of outdoorunit2.5KW |
Room level air cooling precision air conditioner indoor unit |
DAR53-N5-123 |
Refrigerating capacity: 52.69kW. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate:15000m3 /h, E C draught fan, Electric heating capacity 9K W, humidification capacity: 6.5KG/H, size: W1823* D1010* H 1980mm, RS485 communication interface, 7 ''colorful touch screen, double vortex compressor, R410A(not filled), tuyere not included, sinking air supply, top air returning, The height of floor should be higher than 400mm at least; pipes on left at left module; pipes on right at the right module, liquid pipe φ: 15.88, air pipe φ: 22.23, humidifier water supply pipe(19.05mm internal thread) G3/4‘', condensing drain pipeφ19(pagoda joint+hoseclamp),voltage380V, maximum power of indoorunit34.2 KW, maximum power of outdoorunit2*1.2KW |
Room level air cooling precision air conditioner indoor unit |
DAR62-N5-123 |
Refrigerating capacity: 62.40kW. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate: 18000m3 /h, E C draught fan, Electric heating capacity 9K W, 6 .5KG/H Infrared humidifier, size: W1823* D1010* H 1980mm, RS485communication interface, air returning humiture 24℃, 50%RH, 7 ''colorful touch screen, double Danfoss vortex compressor, R410A(not filled), tuyere not included, sinking air supply, top air returning, The height of floor should be higher than 400mm at least; pipes on left at left module; pipes on right at the right module, liquid pipe φ: 15.88, air pipe φ: 22.23, humidifier water supply pipe(19.05mm internal thread) G3/4‘', condensing drain pipe φ19(pagoda joint+hoseclamp), voltage 380V, maximum power of indoor unit 40.1 KW, maximum power of outdoor unit 2*2.2KW |
Room level air cooling precision air conditioner indoor unit |
DAR70-N5-123 |
Refrigerating capacity: 70.11kW. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate:21000m3 /h, E C draught fan, Electric heating capacity 9KW, humidification capacity: 6.5KG/H, size: W1823* D1010* H 1980mm, RS485 communication interface, 7 ''colorful touch screen, double vortex compressor, R410A(not filled), tuyere not included, sinking air supply, top air returning, The height of floor should be higher than 400mm at least; pipes on left at left module; pipes on right at the right module, liquid pipe φ: 15.88, air pipe φ: 22.23, humidifier water supply pipe(19.05mm internal thread) G3/4‘', condensing drain pipeφ19(pagoda joint+hoseclamp),voltage380V, maximum power of indoorunit41.3 KW, maximum power of outdoorunit2*2.2KW |
Room level air cooling precision air conditioner indoor unit |
DAR80-N5-123 |
Refrigerating capacity: 80.22kW. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate:23000m3 /h, E C draught fan, Electric heating capacity 9K W, humidification capacity: 6.5KG/H, size: W1823* D1010* H 1980mm, RS485 communication interface, 7 ''colorful touch screen, double vortex compressor, R410A(not filled), tuyere not included, sinking air supply, top air returning, The height of floor should be higher than 400mm at least; pipes on left at left module; pipes on right at the right module, liquid pipe φ: 15.88, air pipe φ: 22.23, humidifier water supply pipe(19.05mm internal thread) G3/4‘', condensing drain pipeφ19(pagoda joint+hoseclamp),voltage380V, maximum power of indoorunit42.5 KW, maximum power of outdoorunit2*2.2KW |
Room level air cooling precision air conditioner indoor unit |
DAR90-N5-123 |
Refrigerating capacity: 90.03kW. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate: 24000m3 /h, E C draught fan, Electric heating capacity 9K W, 6.5KG/H Infrared humidifier, size: W1823* D1010* H 1980mm, Rs485 communication interface, air returning humiture 24℃, 50%RH, 7 ''colorful touch screen, double Danfoss vortex compressor, R410A(not filled), tuyere not included, sinking air supply, top air returning, The height of floor should be higher than 400mm at least; pipes on left at left module; pipes on right the right module, liquid pipe φ: 15.88, air pipe φ: 22.23, humidifier water supply pipe(19.05mm internal thread) G3/4‘', condensing drain pipeφ19(pagodajoint+hoseclamp),voltage380V, maximum power of indoorunit46.8 KW, maximum power of outdoorunit2*2.5KW |
Room level air cooling precision air conditioner indoor unit |
DAR00-N5-123 |
Refrigerating capacity: 100.22kW. Air returning working condition: dry bulb temperature 24℃, wet-bulb temperature 17℃; Air blowing rate:25600m3 /h, E C draught fan, Electric heating capacity 9K W, humidification capacity: 6.5KG/H, size: W1823* D1010* H 1980mm, RS485 communication interface, 7 ''colorful touch screen, double vortex compressor, R410A(not filled), tuyere not included, sinking air supply, top air returning, The height of floor should be higher than 400mm at least; pipes on left at left module; pipes on right at the right module, liquid pipe φ: 15.88, air pipe φ: 22.23, humidifier water supply pipe(19.05mm internal thread) G3/4‘', condensing drain pipeφ19(pagoda joint+hoseclamp),voltage380V, maximum power of indoor unit 51 KW, maximum power of outdoorunit2*2.5KW |
Room level air cooling precision air conditioner normal temperature outdoor unit |
DAR17-W-N |
Heat dissipating capacity 17kW, using with 12.5kW precision air conditioner indoor unit |
Room level air cooling precision air conditioner normal temperature outdoor unit |
DAR40-W-N |
Heat dissipating capacity 40kW, air blowing 12000m3/h, size W1650*D1100*H1150(with stents), axial draught fan, power 1.32kW |
Room level air cooling precision air conditioner normal temperature outdoor unit |
DAR50-W-N |
Heat dissipating capacity 50kW, air blowing 17000m3/h, size W1650*D1100*H1150(with stents), axial draught fan, power 2.2kW |
Room level air cooling precision air conditioner normal temperature outdoor unit |
DAR70-W-N |
Heat dissipating capacity 70kW, air blowing 21000m3/h, size W2010*D1100*H1150(with stents), axial draught fan, power 2.64kW |
Room level air cooling precision air conditioner normal temperature outdoor unit |
DAR40-W-L |
Heat dissipating capacity 40kW, air blowing 12000m3/h, size W1650*D1100*H1150(with stents), axial draught fan, power 1.32kW, low temperature components |
Room level air cooling precision air conditioner normal temperature outdoor unit |
DAR50-W-L |
Heat dissipating capacity 50kW, air blowing 17000m3/h, size W1650*D1100*H1150(with stents), axial draught fan, power2.2kW, low temperature components |
Room level air cooling precision air conditioner normal temperature outdoor unit |
DAR70-W-L |
Heat dissipating capacity 70kW, air blowing 21000m3/h, size W20101*D1100*H1150(with stents), axial draught fan,power 2.64kW, low temperature components |